FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
FMS to TH140/TH140D Integration
Figure 1.2: Temperature Setup
Figure 1.3: Humidity Setup
1. Set the switch position to mA. Set the temperature range to
50-95 or 32-122. The Sensor is shipped from the factory with
the switch in the volts position and the temperature range is
set for 50-95F. The switch position must be set to the mA
position.
2. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the TH140 Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
Example if Room Temp is 70F and your sensor has a range of 50-95
3. If measured current current does not match calculated current
then check wiring and check TH140/TH140D jumper and switch
settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA =
Room Humidity
100
x 16 + 4
P1
VDC
TB 1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB 2 Inp ut 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB 3 Inp ut 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB 4
NC NO C
RELAY 1
NC NO C
RELAY 2
PWR(4-20 S END)
COMMON
RH OUT (4-20 RTN)
T OUT (4-20 RTN)
RTD/OVERRIDE
RTD/OVERRIDE
SLIDER RIGHT
SLIDER WIPER
SLIDER LEFT
BACK P IECE CENT ER PIECE (WITH CIRCUIT BOARD )
SW1
mAVolts
TEMP 10/5V
TEMP RA NGE
50-95/32-122
TEMP F/C
Out put Select
RH 10/5V
Figure 1.1: FMS Wiring with the TH140/TH140D
1
3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and Offset values. For the 50-95F
range use Gain 11.25, Offset 38.75. For 32-122F range use
Gain 22, Offset 10.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
3
4
5
5
2
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
Formula for calculating the correct RAW value
50 95 Degree F Range
Vista de pagina 0
1 2 3 4 5 6 ... 15 16

Indice de contenidos

Pagina 1 - Figure 1.3: Humidity Setup

SHEET: 1 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 2 - FMS to T120D Integration

SHEET: 10 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 3 - FMS to HEW3MSTA Integration

SHEET: 11 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 4 - FMS to TEAMS Integration

SHEET: 12 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 5 - Figure 5.1: FMS Wiring

SHEET: 13 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 6 - PFM FMS Integration

SHEET: 14 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 7 - GD100 FMS Integration

SHEET: 15 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 8 - AFS-(WM/DM) F200 Integration

SHEET: 16 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0

Pagina 9 - AFS-D FMS Integration

SHEET: 2 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 10 - MD3 FMS Integration

SHEET: 3 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 11 - MDS FMS Integration

SHEET: 4 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 12 - SMK FMS Integration

SHEET: 5 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 13 - Figure 13.1: FMS Wiring

SHEET: 6 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 14 - KPO Falcon Integration

SHEET: 7 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 15 - Temperature Setup

SHEET: 8 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Pagina 16 - -40 - 140 Degree F Range

SHEET: 9 OF 16104 Racquette DriveFort Collins, CO 80524(970) 484-6510 Phone(970) 484-6650 Faxwww.rletech.comFMS Sensor Wiring Guide10061_FMS Rev 2.0 (

Comentarios a estos manuales

Sin comentarios