FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
NC
T-
T+
RH-
RH+
FMS to HEW3MSTA Integration
Figure 3.2: Temperature Setup
Figure 3.3: Humidity Setup
1. The temperature range is 50-95 degF
2. Wire the sensor as shown.
5. Verify the "Calc" Value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current
(+/-1%)
Example if Room Temp is 70F and your sensor has a range of 50-95
3. If measured current current does not match calculated current
then check wiring.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the
following formula to calculate the humidity mA output.
mA =
Room Humidity
100
x 16 + 4
P1
VDC
TB 1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB 2 Inp ut 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB 3 Inp ut 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB 4
NC NO C
RELAY 1
NC NO C
RELAY 2
Figure 3.1: FMS Wiring with the HEW3MSTA
3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and Offset values. For the 50-95F
range use Gain 11.25, Offset 38.75.
4. Configure the Falcon Input Channel (humidity) for "Analog 4-
20mA" and enter the Gain of 25 and Offset of -25.
3
4
5
5
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
Formula for calculating the correct RAW value
50 – 95 Degree F Range
Humidity Signal . Temperature Signal .